GAS Equipment

Anywhere, anytime

LPG
PRESSURE REGULATOR IV

LPG
PRESSURE REGULATOR IV

AUTOMATIC CHANGEOVER PRESSURE REGULATOR
(UNITED & SEPARATED TYPE)

The regulator which automatically executes changeover function from the service side to reserve side for two separate LPG supply lines.
The unitized type is integrated first & second stage pressure reducing portion. Separated type regulator is first stage pressure reducing portion on unitized automatic changeover regulator. This regulator must be combined with second stage regulator for use.

PRESSURE REGULATOR IV - HAC-6

HAC-6

PRESSURE REGULATOR IV - HAC-35

HAC-35

SPECIFICATIONS (UNITIZED TYPE)

Left/Right Scroll
MODEL CAPACITY
(kg/h)
INLET-PRESSURE
(MPa)
SETTING OUTLET
PRESSURE (P2)
OUTLET
-PRESSURE (MPa)
INTERNAL RELIEF WORKING PRESSURE
(kPa)
CONNECTION INTERVAL
(mm)
APPLICATION
INLET OUTLET
HAC-6 6 0.1-1.56 2.8 kPa 2.55-3 .3 7.0 ±1.4 PT 1/4 PT 3/4 Union 81 Household & Commercial
15, 25 kPa (P2) ±Within 20% No Relief
HAC-8 8 2.8 kPa 2.55-3.3 7.0 ±1.4
15, 25 kPa (P2) ±Within 20% No Relief
HAC-12 12 2.8 kPa 2.55-3.3 7.0 ±1.4 PT 1/2 100 Commercial & Regidential
15, 25 kPa (P2) ±Within 20% No Relief
HAC-20 20 2.8 kPa 2.55-3.3 7.0 ±1.4 134
15, 25 kPa (P2) ±Within 20% No Relief
HAC-35 35 2.8 kPa 2.55-3.3 7.0 ±1.4 PT 1 Union
15, 25 kPa (P2) ±Within 20% No Relief

PRESSURE REGULATOR IV - HAX-10

HAX-10

PRESSURE REGULATOR IV - HAX-35

HAX-35

SPECIFICATIONS (SEPARATED TYPE)

Left/Right Scroll
MODEL CAPACITY
(kg/h)
INLET-PRESSURE
(MPa)
SETTING OUTLET PRESSURE (P2) CONNECTION INTERVAL
(mm)
APPLICATION
INLET OUTLET
HAX-10 10 0.1~1.56 0.032~0.083 Mpa PT 1/2B PT 1/2B 100 Household & Commercial & Residential
HAX-15 15
HAX-20 20 134
HAX-35 35